NEW YORK STATE DEPARTMENT OF HEALTH OFFICE OF PUBLIC HEALTHCENTER FOR ENVIRONMENTAL HEALTH
TECHNICAL REFERENCE |
ITEM NO: PWS 14 |
DATE: 11/19/01 |
SUBJECT:
Approved Backflow Prevention Assemblies(Revision)
|
Purpose
The purpose of this Technical Reference is to provide a list of approved backflow prevention assemblies for containing potential contamination as required by
Section 5-1.31 of the State Sanitary Code. This list is made available to regulatory agencies, water purveyors, consulting engineers, manufacturers, certified testers,
contractors and the general public.
Policy
- The New York State Department of Health, Bureau of Public Water Supply Protection (BPWSP) will approve only those backflow prevention
assemblies that have been evaluated in accordance with either of the following evaluation procedures:
- Laboratory and Field Evaluation
Each make, model and size of assembly shall successfully complete the Laboratory and Field Evaluation phases of the Foundation for
Cross Connection Control and Hydraulic Research (FCCC&HR) approval program. Upon completion of the evaluation, the manufacturer
shall submit a copy of the Certificate of Approval issued by the FCCC&HR.
- Laboratory Evaluation Only
Each make, model and size of assembly shall undergo a laboratory evaluation by a qualified independent testing laboratory and shall
comply with the latest editions of each of the following standards, as applicable:
- FCCC&HR Manual of Cross-Connection Control, Section 10 - Specifications of Backflow Prevention Assemblies.
- American Society of Sanitary Engineering (ASSE) Standards:
- 1013 - Reduced Pressure Principle Backflow Preventer
- 1015 - Double Check Backflow Prevention Assembly
- 1047 - Reduced Pressure Detector Assembly Backflow Preventer
- 1048 - Double Check Detector Assembly Backflow Preventer
- American Water Works Association (AWWA) Standards:
- C510 - Double Check Valve Backflow Prevention Assembly
- C511 - Reduced Pressure Principle Backflow Prevention Assembly
Upon completion of the evaluation, the manufacturer shall submit copies of the Laboratory Evaluation Report, ASSE Certificate of
Authorization and AWWA Certificate of Compliance.
In addition to the requirements of 1a or 1b above, the manufacturer shall submit copies of the sales literature and installation/maintenance
literature for each model and size assembly. Sample or cutaway units may also be requested for small diameter assemblies.
All information shall be submitted to the following address:
New York State Department of Health
Bureau of Public Water Supply Protection - Design Section
Flanigan Square
547 River Street, 4th Floor
Troy, NY 12180-2216
(518) 402-7676
- All approved assemblies must include resilient seated, full flow shut off valves integral to the assembly. Unless otherwise approved by the
BPWSP, these shut off valves shall be mounted directly to the assembly and shall be supplied by the assembly manufacturer.
- All approved assemblies are designed for horizontal installation. Certain assemblies on this list are also specifically designed with provisions for
vertical inlet/outlet piping in accordance with the manufacturers recommendations.
To be approved for vertical installation, where vertical refers to the device orientation, the assembly must undergo testing in a vertical position in
accordance with the requirements of 1a or 1b above. Those assemblies that are approved for vertical installation are appropriately designated
on the attached list.
- The BPWSP maintains and periodically updates the list of Approved Backflow Prevention Assemblies. Pages 4-9 reflect currently approved
assemblies as of the date of printing. This list supersedes all previous approvals.
- Previously approved assemblies that are out of production or for which only spare parts are available may not appear on this list. Where such
assemblies are currently installed, however, they may remain in service provided that they are appropriate for the degree of hazard. When these
assemblies demonstrate repeated test failures, require frequent maintenance or if spare parts cannot be readily obtained, they must be replaced by a
currently approved assembly.
- The BPWSP reserves the right to remove from the list any assembly that demonstrates deficient or unsatisfactory operation.
- The following is a partial list of typical manufacturers abbreviations that may appear with the approved model/series designation:
- AG, AGD, AGF - air gap, drain, fitting
- B - full port, resilient seated ball valves
- BB - bronze body
- BF - butterfly valves
- EL - vent elbow
- FAE - flanged adapter ends
- FDA - FDA epoxy coating
- FS - flanged strainer
- FSC - FDA epoxy coated flanged strainer
- HW - hot water unit with stainless steel check valves
- M - manifold, modification
- NRS - non-rising stem shutoffs
- OS&Y - outside stem and yoke shutoffs
- QT - quarter turn resilient seated ball valves
- R, RW - resilient seated or resilient wedge shutoffs
- S - strainer
- SS - stainless steel
- U - union connections
- V - approved for vertical installation in accordance with manufacturers instructions
- XL - high temperature service with removable plastic check seats
- N-Shape - See diagram below for an example (please note that this diagram is not intended to represent any specific manufacturer or device)
- Z-Shape - See diagram below for an example (please note that this diagram is not intended to represent any specific manufacturer or device)
The BPWSP should be contacted with any questions regarding this list.
Reduce Pressure Principle Assemblies
| Company |
Model/Series |
Size (In Inches) |
| AMES |
4000-RP 4000 SS 4000B 4000BM2 |
4.0, 6.0, 8.0, 10.0 0.75, 1.0, 1.5, 2.0, 2.5, 3.0, 4.0, 6.0 0.5, 0.75, 1.0, 1.25, 1.5, 2.0 1.0 |
| BUCKNER |
24000 |
0.75, 1.0, 1.25, 1.5, 2.0 |
| CLA-VAL |
RP-2 RP-4 RP4V RP6LW RP6VW RP7L (W/Y) RP8L (W/Y) RP8N (W/Y) - N Shape RP8V (W/Y) - Z Shape |
0.75, 1.0, 1.25, 1.5 2.0, 2.5, 3.0, 4.0, 6.0, 8.0, 10.0 4.0 0.75, 1.0, 1.25, 1.5, 2.0 0.75, 1.0, 1.5, 2.0 2.5, 3.0, 4.0, 6.0, 8.0, 10.0
2.0, 3.0, 4.0, 6.0, 8.0, 10.0 2.5, 3.0, 4.0, 6.0, 8.0, 10.0 2.5, 3.0, 4.0, 6.0, 8.0, 10.0 |
| CONBRACO |
40-200 40-200-A2S |
0.25, 0.375, 0.5, 0.75, 1.0, 1.25, 1.5, 2.0, 2.5, 3.0, 4.0, 6.0, 8.0, 10.0 0.75, 1.0 |
| FEBCO |
825Y 825YA 825YD 845 860 880 - N Shape 880V - Z Shape |
0.75, 1.0, 1.25, 1.5, 2.0 0.75, 1.0, 1.5, 2.0 2.5, 3.0, 4.0, 6.0, 8.0, 10.0 0.75, 1.0 0.5, 0.75, 1.0, 1.25, 1.5, 2.0, 2.5, 3.0, 4.0, 6.0, 8.0
2.5, 3.0, 4.0, 6.0, 8.0, 10.0 2.5, 3.0, 4.0, 6.0, 8.0, 10.0 |
| FLOMATIC |
RPZ/B9200 RPZII/B9300 B9209 |
0.75, 1.0, 1.5, 2.0, 2.5, 3.0, 4.0 0.5, 0.75 6.0 |
HERSEY/GRINNELL (BEECO) |
FRP-2 6CM |
0.75, 1.0, 1.25, 1.5, 2.0 2.5, 3.0, 4.0, 6.0, 8.0, 10.0 |
| ORION |
BRP |
0.75, 1.0, 1.5, 2.0, 3.0, 4.0 |
| WATTS |
009 U009A 909 909QT 990 994 995QT |
0.5, 0.75, 1.0, 1.25, 1.5, 2.0, 2.5, 3.0 0.75, 1.0, 1.5, 2.0 0.75, 1.0, 1.25, 1.5, 2.0, 2.5, 3.0, 4.0, 6.0, 8.0, 10.0
0.75 ( ), 1.0 ( )
4.0, 6.0, 8.0 2.5, 3.0, 4.0, 6.0 0.5, 0.75, 1.0, 1.25, 1.5 |
| WILKINS |
575A 575 575-M8 575-M10 975XL 975 975XLU 975XLMS 975MS 975BMS 975XLBMS 975XLSE 975XLSE 975XLSEU 975XLSEU 375 475 475V |
0.75, 1.0 1.25, 1.5, 2.0, 2.5, 3.0, 4.0, 6.0 (4"x4"x8" manifold) (6"x6"x10" manifold) 0.25, 0.375, 0.5, 0.75, 1.0, 1.25, 1.5, 2.0
0.75, 1.0, 1.25, 1.5, 2.0, 2.5, 3.0, 4.0, 6.0, 8.0, 10.0 0.75, 1.0, 1.5, 2.0 0.75, 1.0, 1.25, 1.5, 2.0 2.5, 3.0, 4.0, 6.0 2.5, 3.0, 4.0, 6.0, 8.0, 10.0
0.75, 1.0, 1.25, 1.5, 2.0
0.75 ( i o),1.0 ( i o), 1.25 ( i o),
1.5 ( i o), 2.0 ( i o)
0.75 ( i o),1.0 ( i o), 1.25 ( i o),
1.5 ( i o), 2.0 ( i o)
0.75 ( i o),1.0 ( i o), 1.25 ( i o),
1.5 ( i o), 2.0 ( i o)
0.75 ( i o),1.0 ( i o), 1.25 ( i o),
1.5 ( i o), 2.0 ( i o)
2.5, 3.0, 4.0, 6.0, 8.0
4.0 ( i o), 6.0 ( i o)
4.0 ( i o), 6.0 ( i o) |
NOTE:All assemblies are approved for horizontal installation. The following symbols denote devices which are also approved for vertical installation (where vertical refers to the orientation of the device rotated 90 degrees (up or down) from the horizontal) or with vertical inlet/outlet piping:
- vertical up only |
i o - vertical up inlet and vertical down outlet |
- vertical down only |
i o - vertical up inlet and vertical up outlet |
 - vertical up and down |
|
Double Check Valve Assemblies
| Company |
Model/Series |
Size (In Inches) |
| AMES |
2000-DCA 2000 SE 2000 SS 2000B 2000CIV 2001 SS |
4.0, 6.0, 8.0, 10.0 2.5, 6.0 ( ), 8.0 ( )
0.75 ( ), 1.0 ( ), 1.5, 2.0, 2.5 ( ), 3.0 ( ), 4.0 ( ), 6.0 ( ), 8.0, 10.0
0.5 ( ), 0.75 ( ), 1.0, 1.25 ( ), 1.5 ( ), 2.0 ( )
4.0, 6.0, 8.0, 10.0 3.0 ( ), 4.0 ( ) |
| BUCKNER |
24100 |
0.75, 1.0, 1.25, 1.5, 2.0 |
|
| CLA-VAL |
D-2 D-4 DC6LW DC7L (W/Y) DC8L (W/Y) DC8N (W/Y) - N Shape DC8V (W/Y) - Z Shape |
0.75, 1.0, 1.25, 1.5 2.0, 2.5, 3.0, 4.0, 6.0, 8.0, 10.0 0.75 ( ), 1.0, 1.5, 2.0
2.5, 3.0 ( ), 4.0 ( ), 6.0 ( ), 8.0, 10.0
4.0 ( ), 6.0 ( ), 8.0 ( )
2.5, 3.0, 4.0 ( ), 6.0 ( )8.0
2.5, 3.0, 4.0, 6.0, 8.0 |
| CONBRACO |
40-100 DC |
0.75, 1.0, 1.5, 2.0, 2.5, 3.0, 4.0, 6.0, 8.0, 10.0 0.5 ( ), 2.5 ( ), 3.0 ( ), 4.0 ( ), 6.0 ( ) |
| FEBCO |
805Y 805YD 850 870 870V 870 - N Shape 870V - Z Shape |
0.75 ( ), 1.0, 1.5, 2.0
2.5, 3.0 ( ), 4.0 ( ), 6.0 ( ), 8.0, 10.0
0.5 ( ), 0.75 ( ), 1.0 ( ), 1.25 ( ), 1.5 ( ), 2.0 ( ), 2.5 ( ), 3.0 ( ), 4.0 ( ), 6.0 ( ), 8.0 ( )
4.0 ( ), 6.0 ( ), 8.0
4.0 ( ), 6.0 ( ), 8.0 ( )
2.5, 3.0, 10.0 2.5, 3.0 |
| FLOMATIC |
DCV/B9100 B9107 B9109 |
0.75, 1.0, 1.5, 2.0, 2.5, 3.0 4.0 6.0 |
HERSEY/GRINNELL (BEECO) |
FDC HDC No. 2 |
0.75, 1.5, 2.0 0.75, 1.0, 1.5, 2.0 3.0, 4.0, 6.0, 8.0, 10.0 |
| KENNEDY |
1373 |
4.0, 6.0, 8.0, 10.0 |
| ORION |
BDC |
0.75, 1.0, 1.5, 2.0, 3.0, 4.0 |
| WATTS |
007 709 774 774X 775 775QT |
0.50 ( ), 0.75 ( ), 1.0 ( ), 1.5 ( ), 2.0 ( ), 2.50 ( ), 3.0 ( )
0.75 ( ), 1.0 ( ), 1.25 ( ), 1.5 ( ), 2.0 ( ), 2.5 ( ), 3.0 ( ), 4.0 ( ), 6.0 ( ), 8.0 ( ), 10.0 ( )
0.75, 1.0, 1.25, 1.5, 2.0, 2.5, 3.0, 4.0 ( ), 6.0 ( ), 8.0
6.0 ( ), 8.0 ( )
3.0 ( ), 4.0 ( )
0.5 ( ), 0.75 ( ),1.0 ( ), 1.25 ( ), 1.5 ( ) |
| WILKINS |
550A 550 550-M8 550-M10 950 950XL 950XLT 950XLU 350 450 |
0.75, 1.0 1.25, 1.5, 2.0, 2.5, 3.0, 4.0, 6.0 (4"x4"x8" manifold) (6"x6"x10" manifold)
0.75, 1.0, 1.25, 1.5, 2.0, 2.5 ( ), 3.0 ( ), 4.0 ( ), 6.0 ( ), 8.0 ( ), 10.0 ( )
0.75 ( ), 1.0, 1.25, 1.5, 2.0 0.75, 1.0 0.75, 1.0, 1.5, 2.0
2.5 ( ), 3.0 ( ), 4.0 ( ), 6.0 ( ), 8.0 ( )
4.0 ( i o), 6.0 ( i o) |
NOTE:All assemblies are approved for horizontal installation. The following symbols denote devices which are also approved for vertical installation (where vertical refers to the orientation of the device rotated 90 degrees (up or down) from the horizontal) or with vertical inlet/outlet piping:
- vertical up only |
- vertical up inlet and vertical down outlet |
- vertical down only |
- vertical up inlet and vertical up outlet |
- vertical up and down |
|
Double Check Detector Assemblies
| Company |
Model/Series |
Size (In Inches) |
| AMES |
3000 DCDA 3000 SE 3000 SS 3000B 3000CIV 3001 SS |
4.0, 6.0, 8.0, 10.0 2.5, 6.0 ( ), 8.0 ( )
2.5 ( ), 3.0 ( ), 4.0 ( ), 6.0 ( ), 8.0, 10.0
2.0 4.0 ( ), 6.0 ( ), 8.0 ( ), 10.0 ( )
3.0 ( ), 4.0 ( ) |
| CLA-VAL |
DD7LY DD8LY DD8NY - N Shape DD8VY - Z Shape |
3.0, 4.0 ( ), 6.0 ( ), 8.0, 10.0
4.0 ( ), 6.0 ( ), 8.0 ( )
4.0 ( ), 6.0 ( ), 8.0
4.0, 6.0, 8.0 |
| CONBRACO |
40-600 DCDA |
3.0, 4.0, 6.0, 8.0, 10.0
2.5 ( ), 3.0 ( ), 4.0 ( ), 6.0 ( ) |
| FEBCO |
806YD 856 876 876V |
3.0, 4.0 ( ), 6.0 ( ), 8.0, 10.0
2.5, 3.0, 4.0 ( ), 6.0 ( ), 8.0 ( )
2.5, 3.0, 4.0 ( ), 6.0 ( ), 8.0, 10.0
2.5, 3.0, 4.0 ( ), 6.0 ( ), 8.0 ( ) |
HERSEY/GRINNELL (BEECO) |
DDC-II |
3.0, 4.0, 6.0, 8.0, 10.0 |
| WATTS
| 007 DCDA 709 DCDA 774 DCDA 774 XDCDA 775 DCDA |
2.0 ( ), 2.5 ( ), 3.0
3.0 ( ), 4.0 ( ), 6.0 ( ), 8.0 ( ), 10.0 ( )
4.0 ( ), 6.0 ( ), 8.0
6.0 ( ), 8.0 ( )
3.0 ( ), 4.0 ( ) |
| WILKINS |
550 DCDA 950DA 350DA 450DA |
2.5, 3.0, 4.0, 6.0 2.5 ( ), 3.0 ( ), 4.0 ( ), 6.0 ( ), 10.0 ( )
4.0 ( ), 6.0 ( )
4.0 ( i o), 6.0 ( i o) |
NOTE:All assemblies are approved for horizontal installation. The following symbols denote devices which are also approved for vertical installation (where vertical refers to the orientation of the device rotated 90 degrees (up or down) from the horizontal) or with vertical inlet/outlet piping:
- vertical up only |
- vertical up inlet and vertical down outlet |
- vertical down only |
- vertical up inlet and vertical up outlet |
- vertical up and down |
|
Reduced Pressure Detector Assemblies
| Company |
Model/Series |
Size (In Inches) |
| AMES |
5000 RPDA |
4.0, 6.0, 8.0, 10.0 |
| CLA-VAL |
18 RD7LY |
10.0 2.5, 3.0, 4.0, 6.0, 8.0, 10.0 |
| CONBRACO |
40-700 |
3.0, 4.0, 6.0, 8.0, 10.0 |
| FEBCO |
826YD |
2.5, 3.0, 4.0, 6.0, 8.0, 10.0 |
HERSEY/GRINNELL (BEECO) |
6CM-RPDA |
4.0, 6.0, 8.0, 10.0 |
| WATTS |
909 RPDA |
3.0, 4.0, 6.0, 8.0, 10.0 |
| WILKINS |
375DA 475DA 475DAV 975DA 975MS |
4.0, 6.0
4.0 ( i o), 6.0 ( i o)
4.0 ( i o)
2.5, 3.0, 4.0, 6.0, 8.0, 10.0
8.0, 10.0 |
NOTE:All assemblies are approved for horizontal installation. The following symbols denote devices which are also approved for vertical installation (where vertical refers to the orientation of the device rotated 90 degrees (up or down) from the horizontal) or with vertical inlet/outlet piping:
- vertical up only |
- vertical up inlet and vertical down outlet |
- vertical down only |
- vertical up inlet and vertical up outlet |
- vertical up and down |
|
|